Trusted
TM
Analogue Input FTA T8830
Issue 6 Dec 06 PD-T8830 12
5. Specifications
Voltage Range
18 to 32V dc
Maximum Current (Field Supply)
50mA (fused) per loop
Power Consumption (Field Supply)
0.25W (LED power indicator)
Operating Temperature
-5
0
C to 60
0
C (23
0
F to 140
0
F)
Non-operating Temperature
-25
0
C to 70
0
C (-13
0
F to 158
0
F)
Operating Humidity
5 to 95% RH
Environmental Specifications
Refer to Document 552517
Dimensions
Height
Width
Depth
111mm (4.4ins)
335mm (13.2ins)
51mm (2ins)
Weight
900gms (2lbs)