AC Adjustable Frequency Drives
PowerFlex 700S
129
DC Input Drives
DC input for Frames 1…4 use the same code as AC input. Refer to the tables below for frames 5 and 6.
325V dc Input Drives
325V dc Input ✶ 280V dc Input IP20, NEMA Type 1
Frame
Size
Output Amps
Normal
Duty Hp
Heavy
Duty Hp
Output Amps
Normal
Duty kW
Heavy
Duty kW
Cat. No.
Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
20D…
104 (80)7
115 (120) 175 (160) 40 30 120 (92) 132 (138) 175 (175) 30 22 Y
N104A0ENNANANE 5
130 (104)7
143 (156) 175 (175) 50 40 130 (104) 143 (156) 175 (175) 37 30 Y N130A0ENNANANE 5
154 (130)7
169 (195) 231 (260) 60 50 177 (150) 195 (225) 266 (300) 45 37 Y
N154A0ENNANANE 6
192 (154)7
211 (231) 288 (308) 75 60 221 (177) 243 (266) 308 (308) 55 45 Y N192A0ENNANANE 6
260 (205)7
286 (305) 390 (410) 100 75 260 (205) 286 (305) 390 (410) 66 55 Y N260A0ENNANANE 6
✶ Catalog number corresponds to output amps in these columns. Drive must be programmed to lower voltage to obtain higher currents shown at right.
7 Frame 5 and 6 drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be
operated at either rating.
650V dc Input Drives
650V dc Input ✶ 540V dc Input
DC Pre-
charge
IP20, NEMA Type 1
Frame
Size
Output Amps
Normal
Duty Hp
Heavy
Duty Hp
Output Amps
Normal
Duty kW
Heavy
Duty kW
Cat. No.
Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
20D…
96 (77)7
106 (116) 144 (154) 75 60 105 (85) 116 (128) 158 (170) 55 45 N
J096A0ENNANANE 5
96 (77)7
106 (116) 144 (154) 75 60 105 (85) 116 (128) 158 (170) 55 45 Y
R096A0ENNANANE 5
125 (96)7
138 (144) 163 (168) 100 75 125 (96) 138 (144) 163 (168) 55 45 N J125A0ENNANANE 5
125 (96)7
138 (144) 163 (168) 100 75 125 (96) 138 (144) 163 (168) 55 45 Y R125A0ENNANANE 5
156 (125)7
172 (188) 233 (250) 125 100 170 (140) 187 (210) 255 (280) 90 75 N
J156A0ENNANANE 6
156 (125)7
172 (188) 233 (250) 125 100 170 (140) 187 (210) 255 (280) 90 75 Y R156A0ENNANANE 6
180 (156)7
198 (234) 270 (312) 150 125
205 (170)
220 (255) 289 (313) 110 90 N J180A0ENNANANE 6
180 (156)7
198 (234) 270 (312) 150 125
205 (170)
220 (255) 289 (313) 110 90 Y
R180A0ENNANANE 6
248 (180)7
➤
273 (270) 372 (360) 200 150
260 (205)
➤
286 (308) 390 (410) 132 110 N J248A0ENNANANE 6
248 (180)7
➤
273 (270) 372 (360) 200 150
260 (205)
➤
286 (308) 390 (410) 132 110 Y R248A0ENNANANE 6
✶ Catalog number corresponds to output amps in these columns. Drive must be programmed to lower voltage to obtain higher currents shown at right.
7 Frame 5 and 6 drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be
operated at either rating.
➤ Rating is limited to 45°C surrounding air.
Rating is limited to 40°C surrounding air.
810V dc Input Drives
810V dc Input ✶ 690V dc Input
DC Pre-
charge
IP20, NEMA Type 1
Frame
Size
Output Amps
Normal
Duty Hp
Heavy
Duty Hp
Output Amps
Normal
Duty kW
Heavy
Duty kW
Cat. No.
Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
20D…
99 (77)7
109 (116) 126 (138) 100 75
98 (82)
108 (123) 127 (140) 90 75 Y
T099A0ENNANANE 5
144 (125)7
158 (188) 216 (250) 150 125 142 (119) 156 (179) 213 (238) 132 110 Y T144A0ENNANANE 6
✶ Catalog number corresponds to output amps in these columns. Drive must be programmed to lower voltage to obtain higher currents shown at right.
7 Frame 5 and 6 drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be
operated at either rating.
Rating is limited to 40°C surrounding air.