Rockwell-automation 140U H-Frame Circuit Breaker Fixed and Adjustable Manual de usuario Pagina 2

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 2
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 1
Effective 01/01
4
5
3
10 in-lb (0.2 Nm)
34-38 in-lb (3.8-4.3 Nm)
10 in-lb (0.2 Nm)
ON
TRIP
OFF
RESET
Push to trip
6
Warning
INSTALL WIRE APPLICABLE
TO THE HIGHEST RATING
SHOWN ON BREAKER.
Note: Mounting hardware included. Use nuts (provided)
if not threading holes in mounting surface.
Note: Endcap is sold separately.
Optional thermal adjustment
H Frame Collar Torque Values
Wire Size Torque
AWG (mm
2
) In-lb
(N
m)
14-10 (2.5-6) 35 (4.0)
8 (10) 40 (4.5)
6-4 (16-25) 45 (5.1)
3-3/0 (35-95) 50 (5.6)
Note: If cover must be
removed for accessory
installation, torque
cover mounting screws
to 6-8 in-lb (.7-.9 N
m).
40752-001
Effective 02/02
Vista de pagina 1
1 2

Comentarios a estos manuales

Sin comentarios