8 XM-940 Dynamic Measurement Terminal Base
Publication GMSI10-IN020C-EN-P - October 2013
Power Requirements
Refer to the XM-124 Standard Dynamic Measurement installation guide,
publication 1440-IN001, for specific power consumption and other
requirements.
Refer to the XM Power Supply Solutions Application Technique, publication
ICM-AP005
, for additional details.
Interconnect Limit
Total current draw through the side connector cannot exceed 3 A. A separate
power connection is necessary if the total current draw of the interconnecting
modules is greater than 3 A.
There are no drawings associated with the XM-124 Standard Dynamic
Measurement Module, catalog number 1440-SDM02-01RA. Be sure that
the installer follows all applicable local and regional requirements for
installation of the product in the planned location and environment.
If the total current draw for a row of modules is greater than 3 A, consider
connecting power to a module near the center of the rail, rather than at a
module on either end. Insure that there is less than 3 A load in either direction
from the module where power is connected.