Product Overview 1-9
Modes of Operation
(Braking Control)
SMB Smart Motor Braking Option
This option can be used in applications that require reduced stopping
times. The SMC-Flex controller incorporates a microprocessor-based
system that applies braking current to a motor without any additional
equipment. This option offers a user-adjustable braking current
setting from 0% to 400% of the motor’s full load current rating.
Further, it provides automatic shut-off at zero speed detection.
Figure 1.10 SMB Smart Motor Braking Option
Note: All braking current settings in the range of 1…100% will
provide 100% braking current to the motor.
100%
Motor Speed
Smart Motor
Braking
Coast-to-Rest
Time in Seconds
Automatic Zero
Speed Shut-Off
Start
Run
Brake
Stop
Time
ATTENTION
!
SMB Smart Motor Braking is not intended to be used
as an emergency stop. Refer to applicable standards
for emergency stop requirements.