All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM026A-EN-P — April 2014 5
Bulletin 1606 Switched Mode Power Supplies
7. Buer Mode
Rated output current nom. 20A
Current limitation min. 20A Electronically limited
Output voltage typ. 22.5V Jumper in position “22.5V xed”
typ.
1V below input
voltage
Jumper in position “Vin –1V”
Ripple and noise voltage max. 200mVpp 20Hz to 20MHz, 50Ohm
Hold-up time min. 0.2s 22.5V, 20A
typ. 0.31s 22.5V, 20A
min. 28s 22.5V, 0.1A
typ. 43s 22.5V, 0.1A
To increase buer current or extend hold-up time, any given number of buer
units can be installed in parallel.
Activation threshold typ. 22.5V
Ju
mper in position “22.5V xed”
Buering starts if terminal voltage falls below 22.5V.
typ. Vin –1V Jumper in position “Vin –1V”
Buering starts if the terminal voltage decreases by
more than 1V. Buering ends when terminal voltage
increases by more than 1V
Voltage changes slower than 0.54V/s will be ignored
unless the voltage is above 22.5V. Below 22.5V
buering starts immediately.
Status lamp
ashes 10Hz
Active signal
low ohmic
Ready signal
high ohmic
Fig. 7-1 Hold-up time
0,1 A
1,0 A
10,0 A
100,0 A
0,1 s 1,0 s 10,0 s 100,0 s
Buffer
Current
typ. ( 22,5 V )
typ. ( 27,8 V )
min . ( 2 2,5 V )