All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM026A-EN-P — April 2014 7
Bulletin 1606 Switched Mode Power Supplies
10. Operating Diagram
Fig. 10-1 Operating diagram
Fig. 10-2 Signals schematic
Ready
t
Active
t
Optocoupler high ohmic
Optocoupler high ohmic
Optocoupler low ohmic
Optocoupler
low ohmic
V
Mains
t
V
Buffer
Capacitor
t
V
out
t
Charging Mode
LED
t
Buffer Mode
Hold-up Time Power Supply
Standby
Mode
10Hz1.25Hz
8 Ready
7 Active
6 +
5,1V
3mA
9 Inhibit
11. Active and Ready Signal, Inhibit Input
Active signal (Pin 7)
low ohmic while buer capacitors are discharging
Signal voltage max. 35Vdc
Signal current max. 10mA
Voltage drop across opto-coupler typ 0.9V / 3V at 1mA / 5mA, while opto-coupler is low ohmic
Leakage current max. 50μA while opto-coupler is high ohmic
Isolation nom. 500Vac Signal port to power port
Ready signal (Pin 8)
low ohmic when buer is fully charged
Signal voltage max. 35Vdc
Signal current max. 10mA
Voltage drop across opto-coupler typ 0.9V / 3V at 1mA / 5mA, while opto-coupler is low ohmic
Leakage current max. 50μA while opto-coupler is high ohmic
Isolation nom. 500Vac Signal port to power port
Inhibit input (Pin 9)
“High” input signal initiates unit shutdown and buer discharge
Signal voltage max. 35Vdc
Signal current max. 4mA current limited
Shut-down threshold min. 6Vdc Unit is in shut-down mode above this threshold level
max. 10Vdc
Isolation nom. 500Vac Signal port to power port
Wiring diagrams are provided in section 20.