14 DeviceNet 1732 ArmorBlock 16-Point I/O, Series A
Publication 1732D-IN002B-EN-E - January 2013
The 1732D-16CFGM12y self-configuring module contains input and output
functionality. These modules do not need to be configured.
If an I/O point is to be an output, dedicate that point as an output with a wired load and
energize it through a control program.
If an I/O point is to be an input, wire the input device as normal and leave the associated
output un-energized at all times.
1732D-OB16M12y Data Definitions
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Consume 0 07 06 05 04 03 02 01 00
Consume 1 015 014 013 012 011 010 09 08
Where: O = Output data
1732D-16CFGM12y Data Definitions
Byte Byte 7 Byte 6 Byte 5 Byte 4 Byte 3 Byte 2 Byte 1 Byte 0
Produce 0 17 16 15 14 13 12 11 10
Produce 1 115 114 113 112 111 110 19 18
Consume 0 07 06 05 04 03 02 01 00
Consume 1 015 014 013 012 011 010 09 08
Where I = Input data O = Output data