A-10 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference
Analog 2 Channel Input
1734-IE2C
2 Channel Analog Current Input
Configuration Data Data Type Default
Value
Valid Data Values
Low Engineering Channel 0 INT 3,277 -32,768 to 32,767
High Engineering Channel 0 INT 16,383 -32,768 to 32,767
Digital Filter Channel 0 INT 0 0 to 10,000 ms
Low Alarm Limit Channel 0 INT 3,113 -32,768 to 32,767
High Alarm Limit Channel 0 INT 16,547 -32,768 to 32,767
Low Low Alarm Limit Channel 0 INT 2,867 -32,768 to 32,767
High High Alarm Limit Channel 0 INT 16,793 -32,768 to 32,767
Range Type Channel 0 SINT 3 3=4-20mA
8=0-20mA
Limit Alarm Latch Channel 0 SINT 0 0=No Latching
1=Alarms Latch
Alarm Disable Channel 0 SINT 0 0=Alarms Enabled
1=Alarms Disabled
Low Engineering Channel 1 INT 3,277 -32,768 to 32,767
High Engineering Channel 1 INT 16,383 -32,768 to 32,767
Digital Filter Channel 1 INT 0 0 to 10,000 ms
Low Alarm Limit Channel 1 INT 3,113 -32,768 to 32,767
High Alarm Limit Channel 1 INT 16,547 -32,768 to 32,767
Low Low Alarm Limit Channel 1 INT 2,867 -32,768 to 32,767
High High Alarm Limit Channel 1 INT 16,793 -32,768 to 32,767
Range Type Channel 1 SINT 3 3=4-20mA
8=0-20mA
Limit Alarm Latch Channel 1 SINT 0 0=No Latching
1=Alarms Latch
Alarm Disable Channel 1 SINT 0 0=Alarms Enabled
1=Alarms Disabled
Notch Filter (Channel 0 & 1) SINT 2 1=50Hz
2=60Hz
4=250Hz
6=500Hz
Real Time Sample (Channel 0 & 1) INT 100 0 to 10,000 ms