Before You Begin
To effectively use your adapter, note the following considerations.
Determine Compatibility
If using the 1734-AENT adapter with a 1756-ENBT module or 1788-ENBT module, use
the following required firmware versions for these bridge modules:
1756-ENBT firmware version 2.3 or greater
1788-ENBT firmware version 1.33 or greater
If you use the BootP/DHCP Utility to assign IP addresses to the adapter, use version 2.3.2
or greater.
Understand Messaging
Class 3 (Explicit Message) requests through the 1734-AENT adapter to a specific
POINT
I/O module do not always receive a response from the I/O modules. Where an
I/O module does not reply to a request, the adapter responds with an error code indicating
a timeout.
Configure Autobaud
The adapter cannot reconfigure an I/O module that you previously configured to operate
at a fixed baud rate. When you reuse a POINT I/O module from another POINT I/O
system, configure the module to autobaud before using it with the adapter.