POINT I/O 2 Port Ethernet Adapter 9
Publication
1734-IN040B-EN-P - December 2009
Before You Begin
To effectively use your adapter, note the following considerations.
Determine Compatibility
RSLogix 5000 version 17 or greater must be used for the 1734-AENTR
Add-on Profile. The 1734-AENTR adapters will accept I/O
connections with the electronic keying for the 1734-AENT. This
allows the 1734-AENTR adapter to be used in a daisy-chain topology
with the 1734-AENT profile used for the 1734-AENTR.
If using the adapter with a 1756-ENBT module, 1768-ENBT module or
an L3xE processor, use the following required firmware versions for
these bridge modules:
1756-ENBT firmware version 4.5 or greater
1768-ENBT firmware version 2.1 or greater
L3xE processor firmware version 17 or greater
If you use the BootP utility to assign IP addresses to the adapter, use
version 2.3.2 or greater.
Understand Messaging
Class 3 (Explicit Message) requests through the 1734-AENTR adapter
to a specific POINT I/O module do not always receive a response
from the I/O modules. In the case where the I/O module does not
reply to the request, the adapter responds with an error code
indicating a time-out.
Establish I/O Connections
When you start a POINT I/O system and establish I/O connections,
the outputs transition to the Idle state, applying Idle state data before
going to Run mode. This occurs even when the controller making the
connection is already in Run mode.