POINT I/O 2 Relay Output Module 13
Publication 1734-IN587B-EN-P - March 2002
ATTENTION
!
• Do not attempt to increase load current or wattage
capability beyond the maximum rating by connecting
2 or more outputs in parallel. The slightest variation
in relay switching time may cause one relay to
momentarily switch the total load current.
• Make certain that all relay wiring is properly
connected before applying any power to the module.
• Total current draw through the wiring base unit is
limited to 10A. Separate power connections to the
terminal base unit may be necessary.
• Use the end cap from your adapter or interface
module to cover the exposed interconnections on the
last mounting base on the DIN rail. Failure to do so
could result in equipment damage or injury from
electric shock.
01 01 0101 01
001
01
1
01 01 01
120V ac
PDN OX2OX2
PDN IB2 IB4IV2 IV4
FPD OX2 OX2 OX2
ac power
bus
CV
L2/N
L1
Wiring with ac
Modules only
Wiring Using a 1734-FPD to
Create a New ac Power Bus
24V dc
42090OX