Rockwell-automation 1734-OX2/C POINT I/O 2 Relay Output Module Manual de usuario Pagina 16

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 20
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 15
16 POINT I/O 2 Relay Output Module
Publication 1734-IN587B-EN-P - March 2002
Indicator Indication Probable Cause
Network Status
Off Device is not on-line
- Device has not completed dup_MAC_id test.
- Device not powered - check module status
indicator
Flashing Green Device is on-line but has no connections in
the established state.
Green Device on-line and has connections in the
established state.
Flashing Red One or more I/O connections in timed-out
state
Red Critical link failure - failed communication
device. Device detected error that prevents it
communicating on the network.
Flashing
Red/Green
Communication faulted device - the device
has detected a network access error and is in
communication faulted state. Device has
received and accepted an Identify
Communication Faulted Request - long
protocol message.
Indicator Indication Probable Cause
I/O Status
Off Output is off.
Yellow Output is on.
Vista de pagina 15
1 2 ... 11 12 13 14 15 16 17 18 19 20

Comentarios a estos manuales

Sin comentarios