Rockwell-automation 1734D-IA16S PointBlock ac 16-Input Module Installa Manual de usuario Pagina 10

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 12
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 9
10 POINTBlock ac 16 Input Module
Publication 1734D-IN001A-EN-P - May 2001
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
-20 to +55
o
C (-4 to +131
o
F)
-40 to 85
o
C (-40 to 185
o
F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
Conductors Wire Size
Category
14 AWG (2.5mm
2
) - 22 AWG (0.25mm
2
) solid or stranded
copper rated @ 75°C or greater
3/64 inch (1.2mm) insulation max
2
1
Terminal Base Screw
Torque
7 pound-inches (0.6 Nm)
Field Wiring Terminations
DeviceNet 1 - Black Wire -V
2 - Blue Wire CAN Low
3 - Bare Wire Drain
4 - White Wire CAN High
5 - Red Wire +V
Field Power Supply 0 - No Connection1 - No Connection
2 - No Connection3 - No Connection
4 - AC return 5 - AC return
6 - AC power 7 - AC power
Mass 13.88 oz/393.50 grams
Agency Certification
(when product is marked)
C-UL Listed
C-UL Class I, Division 2 Groups A, B, C and D certified
UL listed
UL Class I, Division 2 Groups A, B, C and D certified
CE marked for all applicable directives
C-Tick marked for all applicable acts
1 Use this conductor category information for planning conductor routing. Refer to publication 1770-4.1,
“Industrial Automation Wiring and Grounding Guidelines.”
Vista de pagina 9
1 2 ... 5 6 7 8 9 10 11 12

Comentarios a estos manuales

Sin comentarios