Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 13
Install Your Adapter Chapter 2
Terminating Base
Install the POINT I/O
Adapter Module
To install the adapter on the DIN rail prior to installing other base units:
1. Position the adapter vertically above the DIN rail.
2. Press down firmly to install the adapter on the DIN rail, noting that a
locking mechanism locks the adapter to the DIN rail.
3. Set the network address on the network address thumbwheel.
4. Slide the safety end cap up to remove it, exposing the backplane and power
interconnections
.
43787
Mounting hole
Latching mechanism release
Ground connection
Keyswitch
Latching
mechanism hole
ATTENTION: Allow 25.4 mm (1.0 in.) of space between adjacent
equipment for adequate ventilation.
ATTENTION: Do not discard the end cap. Use this end cap to cover the
exposed interconnections on the last mounting base on the DIN rail.
Failure to do so could result in equipment damage or injury from electric
shock.