Publication 1738-IN013A-EN-E - June 2004
ArmorPoint I/O Synchronous Serial Interface (SSI) Absolute Encoder Module, Series A 7
Wire the SSI Absolute
Encoder Module
Following are wiring instructions for the ArmorPoint SSI Absolute
Encoder module.
1738-SSIM23
IMPORTANT
Shield lead can be connected to chassis pin 5 or 12
on the connector.
ATTENTION
Make sure all connectors and caps are securely
tightened to properly seal the connections against
leaks and maintain IP67 requirements.
3
4
5
6
7
8
9
10
11
12
2
1
43681
1738-SSIM23
(view into connector)
Pin 1 - Data +
Pin 2 - Data -
Pin 3 - V +
Pin 4 - V -
Pin 5 - Chassis
Pin 6 - Input 0
Pin 7 - Clock +
Pin 8 - Clock -
Pin 9 - Return (Com)
Pin 10 - Return (Com)
Pin 11 - 24 V dc
Pin 12 - Chassis