SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 5
Publication 1747-IN019G-EN-P - December 2011
This returns the processor to the initial factory conditions.
Use ControlFLASH
1. Launch the ControlFLASH application under Programs>Flash Programming Tools.
2. Verify that the J4 jumper of the SLC 5/05 processor being upgraded is set to Protect.
The daughtercard firmware can only be updated when the J4 jumper is set to Protect.
ATTENTION: Do not interrupt the flash procedure. Once you have begun to download the
firmware for either the daughtercard (step 18) or the motherboard (step 24), the SLC 5/05 is
put into an unrecoverable state if you lose power or communications for any reason.
GND VBB
SLC 500
CAT
SER
SERIAL NO.
PROC. REV.
)
U
L
)
SA
PROCESSOR UNIT
MADE IN USA
LISTED IND. CONT. EQ.
FOR HAZ. LOC. A196
CLASS 1, GROUPS A, B, C AND D, DIV
. 2
FAC
OPERATING TEMPERATURE CODE T3C
1
3
PROTECT
PROGRAM
J4
OS #
SER
FRN
OPERATING SYSTEM INFO
PLACE FRN UPGRADE LABEL HERE
WHITE
RED
+
-
BATTERY
CURRENT REQUIREMENTS: 1A @ 5 VDC
200mA @ 24 VDC