SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 7
Publication 1747-IN019G-EN-P - December 2011
8. Select the appropriate catalog number from the Catalog Number dialog box and click Next.
For Series C Processors, select catalog numbers that are followed by a ‘/C.
The AB_SNMP.DLL – Enter IP Address dialog box appears.
9. Enter the IP address for the processor.
IMPORTANT
Use the IP address that was noted in step 2 of the section, Prior to Running
ControlFLASH on page 3. If the processor has been reset to Initial Factory
Conditions, use an available IP address assigned by your network administrator.