8 SynchLink Bypass Switch Block
Publication 1751-IN003B-EN-P - September 2001
Wiring the Bypass Switch Block
To wire the bypass switch block and connect power:
1. Connect pre-terminated fiber optic cables as shown.
2. Pre-wire the removable connector plug as shown on the switch block label
or below.
3. Insert the removable connector plug into the mating connector receptacle on
the switch block.
Do not look directly into the fiber ports or fiber cable. Light
levels may cause damage to eyesight. The bypass switch block
is a Class 1 LED product.
Connect To
RxIN1 Upstream station transmitter
TxOUT1 Downstrean station receiver
RxIN2 Local station transmitter
TxOUT2 Local station receiver
Connect To pin
+24V dc Power 4
24V dc Common 3
+24V dc Digital Input 2
24V dc Common Digital Input 1
Do not connect 24V dc Common to Chassis Ground.
31248-M
Pin 1 Pin 2 Pin 3 Pin 4
Power Supply and Digital
Input Connect (front view)
31249b-M
Pin 1
Pin 2 Pin 3 Pin 4
Connector receptacle on switch (front view)