1 Publication 1756-UM528A-EN-P - April 2004
Appendix
D
Using Module Tags
Fault and Status Reporting
Between the Module
and Controllers
Sequence of Events modules multicast fault/status data to the
owner-controller. The module maintains a Module Fault Word, the
highest level of fault reporting.
Table D.1 describes the tag that can be examined in ladder logic to
indicate when a fault has occurred for your Sequence of Events
module:
Each bit corresponds to an individual input.
• If a communication fault occurs on the Sequence of Events
module, all 32 bits in the Module Fault Word are set to 1.
• If chatter is detected on any input points, the bit corresponding
to that point is set to 1.
Figure D.1
Table D.1
Tag: Description:
Module Fault
Word
This word provides fault summary reporting. It’s tag name is Fault.
Module Fault Word
42676
Bit 31 Bit 0
A communications fault sets all bits in the Module Fault Word.