
12 Getting Started with ProcessLogix R400.0
Publication 1757-QS040A-EN-P - October 2001
Configuring analog input modules
To configure an analog input module:
1. Double-click the IOM with the name LabAI.
This brings up the window for the 6-channel isolated analog input module
(1756-IF6I).
2. On the IOM Configuration window, select the Main tab and enter the
following parameters:
3. Select the Channel Configuration tab and enter the following parameters for
all channels:
4. Click OK.
In the Project tab, you can see the modules displayed under
Root.
in this field: enter:
IOM Slot Number the slot number containing this module (remember
that chassis numbering begins with 0)
Remote I/O Chassis Mac Address 0 (this indicates module in same rack as controller)
ControlNet Module Slot Number 0
in this field: select:
Input Range 0V to 10V
Notch Filter 60Hz
Comentarios a estos manuales