Getting Started with ProcessLogix R400.0 21
Publication 1757-QS040A-EN-P - October 2001
Enter Alarms
1. Double-click the DATACQ block to display the Parameters window.
2. Click the Alarms tab.
3. Enter these alarms:
4. Click OK.
5. Close the Control Module FIC102.
6. When prompted, click Yes to save changes.
Downloading the Function Block Diagram to the 1757-PLX52
Control Processor Module
Use this method to download your function block diagram to the Control Processor
Module.
1. In the Project tab, click FIC102.
2. From the Toolbar Menu, click the green down arrow to download the
function block diagram.
3. Click OK to load the selected object to the CEE.
IMPORTANT
You must enter the PV High alarm first to enable the PV High
High alarm.
type trip point priority severity
PV High 85 High 0
PV High High 95 Urgent 0