Getting Started with ProcessLogix R500.1 5
Publication 1757-QS500A-EN-P - October 2002
2. ProcessLogix Server at ControlNet address 24 (set in RSLinx Software).
Verify the ControlNet Nodes Using NTools (Network Tools):
1. To view chassis configuration, click StartProgramsProcessLogix Engineering
ToolsNTools.
2. Click OK to acknowledge the warning.
3. Click NetworkToolsSettings.
4. Select the Ping option and click OK.
5. Click NetworkToolsPing.
6. Click the CNB with Network Address 1. This can be found under the Desktop tree
icon in the upper left window.
7. Under the Local Chassis tab, adjust the number of slots in the scroll box to match the
number of slots in your local chassis and click OK.
8. Verify that all I/O modules appear as configured in the chassis.
9. If the I/O modules do not all appear, try the following:
Check the power supply
Reseat the module(s) in the chassis
Adjust the number of Slots in Local Chassis
10. Select NetworkToolsExit.
TIP
For details on configuring the PCIC card in RSLinx, refer to the
ProcessLogix R500.1 Installation and Upgrade Guide, publication
1757-IN500.