20 Compact Combination Fast Analog I/O Module
Publication 1769-IN081A-EN-P - February 2007
The bits are defined as follows:
• SGN = Sign bit in 2’s complement format.
• Real Time Sample Value = Provides the ability to configure the Real Time
Sample Rate.
• ETS = Enable Time Stamping.
• EC = Enable Channel.
• EA = Enable Alarm.
• AL = Alarm Latch.
• EI = Enable Input Process Alarm Interrupt.
• Input Filter Sel ChIx = Input Channel Filter Setting.
• Inpt Dta Fm ChIx = Input Data Format Select.
• Inpt Tp/Rnge Sel ChIx = Input Type/Range Select.
Word 22 SGN Process Alarm High Data Value Channel 3 0
Word 23 SGN Process Alarm Low Data Value Channel 3 0
Word 24 SGN Alarm Dead Band Value Channel 3 0
Word 25 Reserved
Word 26 EC Reserved EHI ELI LC ER FM PM 0 PFE
Word 27 Reserved Outpt Fm ChI0 Reserved Outpt Tp/Rnge Sel
ChI0
Word 28 SGN Fault Value Channel 0 0 0
Word 29 SGN Program (Idle) Value Channel 0 0 0
Word 30 SGN Clamp High Data Value Channel 0 0 0
Word 31 SGN Clamp Low Data Value Channel 0 0 0
Word 32 SGN Ramp Rate Channel 0 0 0
Word 33 Reserved
Word 34 EC Reserved EHI ELI LC ER FM PM 0 PFE
Word 35 Reserved Outpt Fm ChI1 Reserved Outpt Tp/Rnge Sel
ChI1
Word 36 SGN Fault Value Channel 1 0 0
Word 37 SGN Program (Idle) Value Channel 1 0 0
Word 38 SGN Clamp High Data Value Channel 1 0 0
Word 39 SGN Clamp Low Data Value Channel 1 0 0
Word 40 SGN Ramp Rate Channel 1 0 0
Word 41 Reserved