14 Compact™ Solid State 24V dc Source, High Current Output Module
Publication 1769-IN063A-EN-P - March 2003
Fault State, Word 3
Selects the hold last state or user-defined safe
state condition for each individual output on a
system transition from Run to Fault.
Fault Value, Word 4
Defines the fault state value (0=Off, 1=On). Each
output is individually configurable for on or off.
Module Default Condition
The modules default condition is all zeros, which defines these conditions:
Spare/Replacement Module Parts
· Terminal Block: 1769-RTBN18 (1 per kit)
· Door Label: 1769-RL1 (2 per kit)
· Door: 1769-RD (2 per kit)
Word or Bit Affected Condition Applied
Word 0, Bit 0: Program-to-Fault Enable Program Value
Word 1: Program State User-defined Safe State
Word 2: Program Value Off
Word 3: Fault State User-defined Safe State
Word 4: Fault Value Off
Condition Bit Setting
User-defined Safe State 0
Hold Last State 1
Value Bit Setting
Off 0
On 1