Rockwell-automation 1769-OF4CI CompactLogix 1769-OF4CI Module Manual de usuario Pagina 18

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 28
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 17
18 Compact 1769-OF4CI Isolated Analog Output Module
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Input Data File
For each module, slot x, input data file words 2…5 contain the state of the
module’s output data (output data echo) file words 0…3. During normal
operation, these input words represent the analog values that the outputs are
directed to by the control program.
S = General status (over-range, under-range, or low/high clamp
exceeded).
H = Output held bit.
U = Under-range (or low-clamp exceeded) alarm.
O = Over-range (or high-clamp exceeded) alarm.
Word
Bit Position
1514131211109876543210
0 S3S2S1S0
1 H3U3O3 H2U2O2 H1U1O1 H0U0O0
2 Channel 0 Data Value
3 Channel 1 Data Value
4 Channel 2 Data Value
5 Channel 3 Data Value
IMPORTANT
The output module’s input data file reflects the analog output
data echo of the module, not necessarily the electrical state of
the output terminals. It does not reflect shorted or open outputs.
Vista de pagina 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 27 28

Comentarios a estos manuales

Sin comentarios