24 Compact 1769-OF4CI Isolated Analog Output Module
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Specification 1769-OF4CI
Accuracy Drift with Temperature ±0.0058% FS per °C
Output Ripple
(1)
range 0 to 50 kHz
(referred to output range)
±0.05%
Non-linearity (in percent full scale) ±0.05%
Repeatability
(2)
(in percent full scale)
±0.05%
Output Error Over Full Temperature Range
(0 to 60°C [+32 to +140°F])
±0.55%
Output Impedance >1 MΩ
Open and Short-Circuit Protection Yes
Maximum Short-Circuit Current 21 mA
Output Overvoltage Protection Yes
Output Response at System Power Up and
Power Down
No power up or power down current glitch
Rated Working Voltage
(3)
30V ac/30V dc
Output Group to Bus Isolation 500V ac or 710V dc for 1 minute (qualification
test)
30V ac/30V dc working voltage (IEC Class 2
reinforced insulation)
Module OK LED On: module has power, has passed internal
diagnostics, and is communicating over the
bus.
Off: Any of the above is not true.
Channel Diagnostics Over- or under-range by bit reporting
(1) Output ripple is the amount a fixed output varies with time, assuming a constant load and
temperature.
(2) Repeatability is the ability of the output module to reproduce output readings when the same
controller value is applied to it consecutively, under the same conditions and in the same direction.
(3) Rated working voltage is the maximum continuous voltage that can be applied at the output terminal,
including the output signal and the value that floats above ground potential (for example, 10V dc
output signal and 20V dc potential above ground).