20 Compact 1769-OF4VI Isolated Analog Output Module
Rockwell Automation Publication 1769-IN076B-EN-P - August 2010
Channel Configuration Words
• E = Channel Enable: (0 = Disabled, 1 = output Enabled, process
changes)
• Reserved = Set to zero
• SIU = System interrupt low clamp, under-range alarms: (0 = Disabled,
1 = Enabled)
• SIO = System interrupt high clamp, over-range alarms: (0 = Disabled,
1 = Enabled)
• LA = Latch low/high clamp, under/over-range alarms: (0 = Disabled,
1 = Enabled)
• ER = Enable ramping: (0 = Disabled, 1 = Enabled. Ramp rate limited by
fault states.)
• FM = Fault mode: (0 = Hold Last State, 1 = User Defined Value)
• PM = Program mode: (0 = Hold Last State, 1 = User Defined Value)
• HI = Hold for initialization: (0 = Disabled, 1 = Enabled)
• PFE = Program/idle to fault enable: (0 = Disabled, 1 Enabled)
The first two words of each eight word group in the configuration file allow you
to change the parameters of each channel independently. For example, words 8
and 9 correspond to channel 1 while words 16 and 17 correspond to channel 3.
Word/Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
0
Word 0 E Reserved SIU SIO LA ER FM PM HI
PFE
Word 1 Reserved Output Data
Format Select
Reserved Output
Type/Range
Define Indicate
this
These bit settings
1514131211109876543210
Program
(Idle) to Fault
Enable
Program (Idle)
Mode Data
Applied
(1)
0
Fault Mode
Data
Applied
(1)
1