6 Compact 1769-OF4VI Isolated Analog Output Module
Rockwell Automation Publication 1769-IN076B-EN-P - August 2010
System Assembly
The module can be attached to the controller or an adjacent I/O module before
or after mounting.
• For mounting instructions, see Panel Mounting
on page 9, or DIN Rail
Mounting on page 11.
• To work with a system that is already mounted, see Replacing a Single
Module Within a System on page 11.
ATTENTION: Remove power before removing or inserting this
module. When you remove or insert a module with power applied,
an electrical arc may occur. An electrical arc can cause personal
injury or property damage by:
• sending an erroneous signal to your system’s field devices,
causing unintended machine motion.
• causing an explosion in a hazardous environment.
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance.
Comentarios a estos manuales