Programming ExamplesB–4
  !  
2. Press [F8],[F5] and enter N7:60 to display the configuration
block.
The industrial terminal screen should like figure B.3.
Figure B.3
Sample PLC-5 Data File (Hexidecimal Data)

















The above data file would configure the module as follow:
copper RTDs on all inputs
temperature scale of Fahrenheit
channel 1 displayed in ohms
output data in BCD format
real time sampling set to a 1 second scan rate
copper RTD at 25
o
C is 9.76 ohms
all bias values set to subtract 0150
all calibration values set to 0
3. Enter the data corresponding to your bit selections.
4. [ESC] returns you to the main menu.