Choosing a Backup Configuration
Chapter 1
1-7
The three methods of switching control of outputs from the primary to the
backup processor are:
automatic switchover with no switchback
automatic switchover with controllable switchback
manual switchover
You can use any one of these methods for scanner backup, but you must
use automatic switchover with controllable switchback for MX backup.
Table 1.C lists the attributes associated with each method.
Table 1.C
Switchover
Method Attributes
Switchover
Method:
Attributes:
Automatic
Switchover with
No Switchback
 Backup processor automatically takes control of outputs when the primary
processor faults.
 No operator intervention required at switchover.
 Shutting off the primary processor initiates switchover.
 Both the primary and the backup processor must be shut down and
restarted when reinstalling a repaired processor.
 Not recommended for applications using multidrop modems with 1775KA
modules because the modem port is not disabled after a processor fault.
Automatic
Switchover with
Controllable
Switchback
 Backup processor automatically takes control of outputs when the primary
processor faults.
 No operator intervention required at switchover.
 Shutting off the primary processor initiates switchover.
 Either processor can be the primary" processor.
 The backup processor does not have to be shut down when reinstalling a
repaired primary processor.
 Not recommended for applications using multidrop modems with 1775KA
modules because the modem port is not disabled after a processor fault.