Installing a Backup System
Chapter 2
2-23
Terminators
The first and last physical device of each I/O channel requires a terminator.
Use discrete terminators (cat. no. 1770-XT) for 1775-S4A, -SR scanner
modules. The 1775-S5, -SR5 scanner modules have internal terminators
that can be enabled/disabled with a switch. See Figure 2.17 and Figure 2.7.
Figure 2.17
Selecting
T
erminators on 1775S5, SR5 Scanner Modules
1234
Switch Positions:
UP =
Switch is away from board
DOWN =
Switch is toward board
When DOWN, a terminator is connected on the corre
sponding communication channel.
Connect a terminator when the scanner is physically
the first or last device on a Data Highway
, Data High
way Plus, I/O, peertopeer
, or backup communica
tions link; otherwise, set the switch to the UP position.
ON
OFF
ON
OFF
OFF
ON
10979I
Important: When using internal terminators, removing the terminal
swing arm from a module causes the communication channels to be
unterminated.
For more information about terminators and I/O channel wiring, refer to
the PLC-3 Programmable Controller Installation and Operation Manual
(publication 1775-6.7.1).