ControlNet NetChecker 23
Rockwell Automation Publication 1788-UM001B-EN-P - August 2012
Impedance mismatches cause reflections on the media:
Network not correctly terminated.
Impedance of coaxial cable not equal to 75
Ω.
High resistance of contact in connectors.
Incorrect network architecture.
Effect of Attenuation on Signal Edges
Excessive attenuation causes loss of signal:
Poor quality coaxial cable
Resistance too high
Losses in dielectric
Overloaded network
Too long trunk seg m ent
Excessive number of nodes per segment
Impedance mismatches
IMPORTANT
Each coaxial segment must be terminated with a 1786-TCAP terminator at each end.
2.000 V/D
100 ns/DIV