Publication 1788-UM052B-EN-P - April 2002
Troubleshooting and Common Questions B-3
Device Problems
If you receive a status of Bad:Device Failure, set the RESTART
parameter in the Block window to Processor or Default. If the
problem persists, replace the device.
If a device does not accept a permanent address, you must set the
device tag. For instructions on setting the tag, refer to the Setting
Device or Block Tags on page 4-5. If the device already has a tag, the
T3 network parameter might not be the right length. To solve this
problem, remove the device from the active bus and configure its
address separately.
If a device does not accept a new tag, it might be in an invalid state.
To solve this problem, power the device off and on.
Missing Devices
If a device does not appear in the Project window, complete these
steps:
1. Check all connections.
2. Power on the bus.
3. Select Start
Programs NI-FBUS Interface Config and
click on the Advanced button.
4. Set the following parameter values.
5. Select Start
Programs NIFBUS nifb to restart the nifb
process.
6. Select Start
Programs NIFBUS NI-FBUS Configurator
to restart the NI-FBUS Configurator.
Parameter Value
Number of unavailable nodes 0
InterPduDelay 20
Slot time 10
Max reply delay 8