DeviceNet Digital Base D-shell Block CompactBlock LDX I/O 17
Publication
1790-IN013A-EN-P - September 2006
All digital-expansion inputs produce data of 0 if the expansion cable
is removed. No status is in the default produced assembly. Attribute
101 in the identity object reports module faults.
If no faults are present, an explicit message GET command returns 0.
If the ribbon cable is disconnected, it returns 0x04, which is for
module location change. The module LED indicator also flashes
indicating a fault if an expansion is disconnected. Select an alternate
produced assembly that contains the expansion status byte, using the
EDS Properties configuration window.
Specifications
IMPORTANT
Input and output wiring must be in accordance with Class 1, Division 2 wiring
methods and in accordance with the authority having jurisdiction.
1790D-16BVO Universal dc Input Base Block
Attribute Value
Inputs per Module 16 point, sinking or sourcing
On-state Voltage 9.6V dc min, 24V dc nom, 28.8V dc max
Off-state Voltage 5.0V dc max
On-state Current 8 mA max per channel @ 28.8V dc
Input Impedance, Nom 4.8 kΩ
Field Power Dissipation 3.68 W max @ 28.8V dc
Isolation Voltage 50V dc (continuous), reinforced insulation type,
tested at 1250V ac for 60 s, I/O to system