Radiated RF Immunity EC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 80…1000 MHz
10V/m with 1 kHz sine-wave 80%AM from 1.4…2 GHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
EFT/B Immunity IEC 61000-4-4
+
2 kV at 5 kHz on signal ports
+
2 kV at 5 kHz on communication ports
Surge Transient Immunity IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±2 kV line-earth(CM) on communications ports
Conducted RF Immunity IEC61000-4-6
10V rms with 1 kHz sine-wave 80%AM at 150 kHz...80 MHz
Enclosure Type Rating Meets IP20
Mounting DIN rail or panel
Dimension 52 x 104 x 42 mm (2.03 x 4.07 x 1.64 in.)
Weight 0.1 kg (0.3 lb)
Wiring Category
(1)
2 - on signal ports
2 - on communication ports
Wiring 37-pin D-shell connector
DeviceNet
DeviceNet Power Supply voltage - 24V dc nom
Voltage range - 11…28V dc
DeviceNet Power
Dissipation
1.2 W max @ 28.8V dc
Network Length 500 m (1640 ft) max @ 125 Kbps
100 m (328 ft) max @ 500 Kbps
Environmental Specifications Common To All Base Blocks in This Publication
Attribute Value