Installation Instructions
Block I/O
Cat. No. 1791-32A0 Series B
10
Indicators
PLC SLC
ININ
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
COMM
STATUS
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
COMM
STATUS
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
G G+1
ININ
G G+1
Indicator Description
COMM
OFF
ON
Flashing
Communication not established
Communication established
Processor in Program mode
STATUS OFF
ON
Flashing
Normal
Error (hardware or software), block power low
COMM F
AIL – communication cable disconnected, 100ms between valid frames, no
more than 255 valid frames between valid frames addressed to block, 20ms idle
time exceeded.
COMM
and ST
A
TUS will alternately flash when processor restart lockout is selected, a fault has occurred and the processor
is communicating with the block.
Fusing
The block I/O module is internally fused to protect the module. No external
power fusing is required.