35
ArmorBlock 2 Input/2 Output Module
Publication 1792-5.5 – October 1996
2 Input/2 Output Module – 1792-IB2XOB2E/B
General Specifications
Indicators Mod/Net Status – red/green
Input Fault – red
I/O Status – yellow/red (customer field side driven)
DeviceNet Power Voltage
Current
11.0 – 25.0V dc
100mA (no powered sensors)
200mA (full sensor load)
Surge Current at Power Up Less than 10A for 5ms
Dimensions Inches
Millimeters
2.6H X 7.7W X 3.06D
66H X 195W X 77.7D
Connectors 1792-IB2XOB2EA/B – Aluminum connectors
1792-IB2XOB2ES/B – Stainless Steel Connectors
Power Dissipation Maximum 1.9 Watts
Thermal Dissipation Maximum 6.9 BTU/hr
Isolation Voltage 500V ac – outputs to DeviceNet
500V ac – outputs to inputs
Specifications continued on next page