ArmorBlock LP2 16 Sourcing Input Module 5
Publication 1792D-5.28 - January 1999
Communicate With Your ArmorBlock LP2 Module
This ArmorBlock module’s I/O is exchanged with the master through a
polled, change of state, or cyclic connection.
The module produces input data as follows:
Cyclic - allows configuration of the block as an I/O client. The block will
produce its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O
message to the module. The 16 input module scans the inputs producing a
response that reflects their status.
Change of state - productions occur when an input changes. If no input
change occurs within the expected packet rate, a heartbeat production
occurs. This heartbeat production tells the scanner module that the module
is alive and ready to communicate.
Refer to the table below for the word/bit definitions.
\
The DeviceNet Network uses advanced network technology, producer/
consumer communication, to increase network functionality and
throughput. Visit our website at http://www.ab.com/networks for producer/
consumer technology information and updates.
Type of I/O Connections Consumes Produces
Cyclic 0 Byte 2 Bytes
Polled 0 Byte 2 Bytes
Change of State 0 Byte 2 Bytes
Bit 0706050403020100
Produces 0
I7 I6 I5 I4 I3 I2 I1 I0
Produces 1
I15 I14 I13 I12 I11 I10 I9 I8
Where:OW = Off Wire I = Input
Byte Bit Description
Produces 0
00-07 Input status bits: When the bit is set (1), the input is on. Bit
00 = input 0, bit 01= input 1, bit 02 = input 2, bit 03 =
input 3, bit 04 = input 4, bit 05 = input 5, bit 06 = input 6,
bit 07 = input 7
Produces 1
00-07 Input status bits: Bit 00 = input 8, bit 01= input 9, bit 02 =
input 10, bit 03 = input 11, bit 04 = input 12, bit 05 = input
13, bit 06 = input 14, bit 07 = input 15