Rockwell-automation 1792D-16VT0LP INSTL INSTR ARMORBLOCK INPUT Manual de usuario Pagina 7

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 8
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 6
7 ArmorBlock LP2 16 Sourcing Input Module
Publication 1792D-5.28 - January 1999
Specifications
Network Status Indicator
Indication Status
None Not On-line
Green
Blinking
Solid
On-line/No Connections
On-line/Connected
Red
Blink
Solid
Connection Timed Out
Failed Communication: A duplicate
node address exists or the module is at
the wrong baud rate.
I/O Status Indicators
Function Module Status Indicator
Point Indicator
Condition
Inputs Green
Green
None
Yellow
No valid input
Valid input
16 Input Module - Cat. No. 1792D-16VT0LP
Sourcing Input Specifications Max Min
Inputs per block 16 - 3 wire or dry contact NPN devices or 8 - 4 wire
NPN devices
Sensor Source Current (per input) 50mA per point
Off-Wire Sense Current 0.5mA -
On-state Voltage 25V dc 10V dc
On-state Current 10mA 2mA
Off-state Voltage 5V dc
Off-state Current 1.5mA
General Specifications
Indicators Network Status - red/green
Module Status - red/green
Point LED - yellow
Communication Rate 125Kbps @ 500 meters(1600 feet) for thick
cable, flat media length 375 meters
250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters
500Kbps @ 100 meters (330 feet) for thick
cable, flat media length 75 meters