4 FLEX Integra 4 Protected Output Module
Publication 1793-5.2 - January 2000
Wiring
This module is available with 2 styles of connectors; screw-cage and
spring-clamp. Refer to the wiring figure below.
1. Connect individual output wiring to terminals 2 through 5 on row A.
2. Connect associated common to terminals 10 through 13 on row B.
3. Connect +24V dc voltage to terminal 8 on row B.
4. Connect 24V dc common to terminal 0 on row A.
5. If daisy-chaining +24V dc from this module to the next FLEX Integra
module, connect a jumper from terminal 15 to terminal 8 on the next
Integra module.
6. If daisy-chaining 24V dc common from this module to the next FLEX
Integra module, connect a jumper from terminal 7 on this module to
terminal 0 on the next Integra module.
.
!
ATTENTION: Total current draw through the module’s
(+) voltage terminals is limited to 10A. Separate power
connections to the module may be required.
1793-OB4P
1793-OB4PS
01234 567
8 9 10 11
A
B
13 14 1512
41432
CV CV
CCVVCCVV
OOOO
Ch 0
Ch 1
Ch 2
Ch 3
0 123456 7
8 9 10 11 12 13 14 15
A
B
41380
CV CV
CCVVCCVV
OOOO
Ch 0
Ch 1
Ch 2
Ch 3
Where: C = common, V = + voltage and O = output