Thermal Dissipation 4.4 BTU/hr @ 31.2V dc
Indicators 4 yellow channel status indicators
External dc Power Voltage
Current
19..2-31.2V dc (5% ac ripple)
80mA
Dimensions 2.72H x 3.15D x 2.17W
(69H x 80D x 55W)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Nonoperating
Vibration
0 to +55
o
C (32 to +131
o
F)
-40 to +85
o
C (-40 to +185
o
F)
5 to 95% noncondensing
Tested to 30g peak acceleration, 11(+
1)ms pulse width
Tested to 50g peak acceleration, 11(+
1)ms pulse width
Tested 5g @ 10-500Hz per IEC68-2-6
Conductors Wire Size
Category
12 gauge (4mm
2
) to 18 gauge (0.75mm
2
) stranded
wire rated @ 75
o
C minimum
3/64 in (1.2mm) maximum insulation
2
1
Screw Terminal Torque 5-7 lb-in (0.5-0.6Nm)
Agency Certification
(when product is marked)
CUL Listed
CUL Class I, Division 2 Groups A, B, C and D certified
UL listed
CE marked for all applicable directives
C-Tick marked for all applicable acts.
1 Use this category information for planning conductor routing as described in publication 1770-4.1, “Wiring and
Grounding Guidelines for Noise Immunity.”