FLEX I/O 8 Input HART Analog Module 25
Publication
1794-IN108D-EN-P - January 2014
Remote Transmitter Error Up/Down (Series A Mode)
Word 0 Bit 08 Up/down for Channels 0...3
Word 1 Bit 08 Up/down for Channels 4...7
Where: O = up
1 = down
Data Format (Series A Mode)
Word
Bits
D
escription
0 04 03 02 01 Channels 0...3
1 04 03 02 01 Channels 4...7
0000022 mA = 0...22,000 with error steps (default)
0001022 mA = 0110%, with error steps
0010022 mA = 0104.8%, square root, with error steps
0011020 mA = 065,535, unsigned integer, with error steps
0100222 mA, with error steps
0101222 mA = -12.5%112.5%, with error steps
0110422 mA = 0106%, square root, with error steps
0111420 mA = 065,535, unsigned integer, with error steps
1000Not assigned
1001Not assigned
1010Not assigned
1011022 mA = A/D count, with fixed error
11003.621 mA = NAMUR NE 43, with fixed error
1101321 mA = -6.25 to 106.25% with fixed error
1110222 mA = -12.5 to 112.5% with fixed error
1111Not assigned