Publication 1794-UM065B-EN-E - September 2010
138 Use the 1794-OF8IH Module with the Generic Profile
Channel Analog Fault Mode Selection
Analog Fault Mode Decimal Value Bits
98
10
Min Scale 0 0 0
Max Scale 1 0 0
Hold Last State 2 1 0
User Specified Data Value 3 1 1
Fault Latch Enable
Channel Bits
0 [Adapter Name]:[Slot]:C.Data[4].2
1 [Adapter Name]:[Slot]:C.Data[4].10
2 [Adapter Name]:[Slot]:C.Data[5].2
3 [Adapter Name]:[Slot]:C.Data[5].10
4 [Adapter Name]:[Slot]:C.Data[6].2
5 [Adapter Name]:[Slot]:C.Data[6].10
6 [Adapter Name]:[Slot]:C.Data[7].2
7 [Adapter Name]:[Slot]:C.Data[7].10
Latch Mode Bit 0
Unlatched 0
Latched 1
HART Current Ratio
Channel Bits
0 [Adapter Name]:[Slot]:C.Data[4].3
[Adapter Name]:[Slot]:C.Data[4].4
[Adapter Name]:[Slot]:C.Data[4].5
[Adapter Name]:[Slot]:C.Data[4].6
[Adapter Name]:[Slot]:C.Data[4].7
1 [Adapter Name]:[Slot]:C.Data[4].11
[Adapter Name]:[Slot]:C.Data[4].12
[Adapter Name]:[Slot]:C.Data[4].13
[Adapter Name]:[Slot]:C.Data[4].14
[Adapter Name]:[Slot]:C.Data[4].15