16 Micro830 16 Point Programmable Controllers
Publication 2080-IN003B-EN-P - April 2014
Current, per common,
max
5 A N.A.
Turn on time/
Turn off time, max
10 ms 2.5 μs ON: 0.1 ms
OFF: 1 ms
(1)
Applies for general purpose operation only. Does not apply for high-speed operation.
Relay Contacts Ratings
Maximum Volts Amperes Amperes
Continuous
Volt-Amperes
Make Break Make Break
120V AC 15 A 1.5 A 2.0 A 1800V A 180V A
240V AC 7.5 A 0.75 A
24V DC 1.0 A 1.0 A 28V A
125V DC 0.22 A
Environmental Specifications
Attribute Value
Temperature,
operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)
Temperature,
surrounding air, max
65 °C (149 °F)
Temperature,
non-operating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Output Specifications
Attribute Relay Output
(2080-LC30-16AWB,
2080-LC30-16QWB
only)
High Speed Output
(2080-LC30-16QVB
only)
(Outputs 0...1)
Standard Output
(2080-LC30-16QV
B only)
(Outputs 2....5)
Comentarios a estos manuales