8 Resolver Feedback Option Card for PowerFlex® 700S Drives
Step 6: Wiring the Resolver
Feedback Option Card to a
Resolver
Terminal block P1 contains connection points for a resolver. This terminal
block resides on the Resolver Feedback Option card
.
TIP: Remember to route wires through the sliding access panel at the
bottom of the Control Assembly.
Terminal Signal Description
8 REF HIGH Positive Reference signal
7 SHIELD Connection point for resolver cable
shield
6 REF LOW Negative Reference signal
5 SIN HIGH Positive Sine signal
4 SHIELD Connection point for resolver cable
shield
3 SIN LOW Negative Sine signal
2 COS HIGH Positive Cosine signal
1 COS LOW Negative Cosine signal
12345 6 78