Installation Instructions
PowerFlex
®
DC Drive - Frame C Field SCR
Module
What This Kit Includes
Field SCR module
Two screws and washers
Two gate leads
Thermal grease
Static strap
Important:It is highly recommended that the Field Snubber circuit board
and Field Dual Diode module be replaced when replacing the
Field SCR module. The Field Snubber circuit board and Field
Dual Diode module are sold as separate spare part kits.
Tools That You Need
Phillips
®
screwdriver
Flathead screwdriver
Phillips
®
is a registered trademark of Phillips Screw Company.
!
ATTENTION: Only qualified personnel familiar with DC
drives and associated machinery should plan or implement the
installation, start-up and subsequent maintenance of the system.
Failure to comply may result in personal injury and/or equipment
damage.
!
ATTENTION: To avoid an electric shock hazard, ensure that
all power to the drive has been removed before performing the
following.
!
ATTENTION: This drive contains ESD (Electrostatic
Discharge) sensitive parts and assemblies. Static control
precautions are required when installing, testing, servicing or
repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with
static control procedures, reference A-B publication 8000-4.5.2,
“Guarding Against Electrostatic Damage” or any other
applicable ESD protection handbook.
Vista de pagina 0
1 2 3 4 5 6 7 8 9 10

Indice de contenidos

Pagina 1 - PowerFlex

Installation InstructionsPowerFlex® DC Drive - Frame C Field SCR Module What This Kit Includes• Field SCR module• Two screws and washers• Two gate le

Pagina 2 - What You Need to Do

Publication 20P-IN047A-EN-P - March 2009Copyright © 2008 Rockwell Automation. All rights reserved. Printed in USA.www.rockwellautomation.comAmericas:

Pagina 3 - Step 1: Remove Power

2 PowerFlex® DC Drive - Frame C Field SCR Module What You Need to DoThe Field SCR module is located below the Field Snubber circuit board in the upper

Pagina 4 - Protective Covers

PowerFlex® DC Drive - Frame C Field SCR Module 3 Step 1: Remove Power from the Drive1. Remove and lock-out all incoming power to the drive. !ATTENTION

Pagina 5 - Shield and Control Board

4 PowerFlex® DC Drive - Frame C Field SCR Module Step 2: Remove the Protective Covers1. Disconnect the DPI cable from the HIM assembly (if present).2.

Pagina 6 - Remove cable

PowerFlex® DC Drive - Frame C Field SCR Module 5 4. Disconnect the HIM Communication cable from the connector on the upper right corner of the Control

Pagina 7 - Field SCR Module

6 PowerFlex® DC Drive - Frame C Field SCR Module 2. Loosen the two captive screws at the top of the Control EMI shield and partially lower the shield.

Pagina 8 - Remove screws

PowerFlex® DC Drive - Frame C Field SCR Module 7 Figure 1 Field Snubber Board LayoutStep 4: Remove the Field Snubber Board and Existing Field SCR Mo

Pagina 9 - Step 6: Install the EMI

8 PowerFlex® DC Drive - Frame C Field SCR Module 3. Remove the (orange and yellow) cables from connectors K1G1 and K2G2 on the top left side of the Pu

Pagina 10 - Related Documentation

PowerFlex® DC Drive - Frame C Field SCR Module 9 Step 5: Install the Field Snubber Board and New Field SCR ModuleInstall the Field Snubber board and n