Publication 20P-IN056A-EN-P
6
Step 4: Remove the
Existing Field Dual Diode
Module
Remove the two screws and washers that secure the dual diode module to the
heatsink and remove the module.
Figure 3 Dual Diode Module
Step 5: Install the New
Field Dual Diode Module
Install the new field dual diode module in reverse order of removal as detailed in
Step 4: Remove the Existing Field Dual Diode Module
above.
Apply thermal grease to the bottom of the dual diode module before securing
it to the heatsink.
Step 6: Install the Field
Board
Install the field board in reverse order of removal as detailed in Step 3: Remove
the Field Board on page 4.
Dual diode module
Tightening torque:
2.5…5.0 N•m
(22…44 lb•in)
P2
ATTENTION: Thermal grease must be applied to the bottom of the
field dual diode module before securing it to the heatsink or damage
to the drive may occur.