2 Rockwell Automation Publication 20P-IN071B-EN-P - June 2011
PowerFlex
®
DC Drive Resolver Feedback Option Module
What You Need to Do
To install the resolver feedback option module:
Step 1: Remove power from the drive
Step 2: Open the drive
Step 3: Install the resolver interface board
Step 4: Install the resolver feedback board
Step 5: Wire the resolver interface and feedback boards
Step 6: Replace the protective covers and configure the resolver feedback
option module
Step 1: Remove Power
from the Drive
Remove and lock-out all incoming power to the drive.
Step 2: Open the Drive To open frame A drives see Frame A Drives on page 3.
To open frame B and C drives see Frame B and C Drives
on page 4.
To open frame D drives see Frame D Drives
on page 4.
ATTENTION: Remove power before making or breaking cable
connections. When you remove or insert a cable connector with power
applied, an electrical arc may occur. An electrical arc can cause personal
injury or property damage by:
sending an erroneous signal to your system’s field devices, causing
unintended machine motion
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module
and its mating connector. Worn contacts may create electrical resistance.
L1 L2 L3
O
I