Upgrade Kit InstructionsDC Link Fuse Upgrade Kit for RGU in Parallelwith NRUContentsThis document shows how to install the DC Link Fuse Upgrade Kit fo
10 DC Link Fuse Upgrade Kit for RGU in Parallel with NRUFigure 11 New Relay Contacts In Enable and External Not Fault CircuitsFigure 12 External Not F
DC Link Fuse Upgrade Kit for RGU in Parallel with NRU 11Testing• Energize the unit• Remove wire 117 or 119 from the coil of the relay. Use caution whe
12 DC Link Fuse Upgrade Kit for RGU in Parallel with NRUPublication 2364F-5.24 – February, 2001 P/N304946Copyright 2001 Rockwell International Corpora
2 DC Link Fuse Upgrade Kit for RGU in Parallel with NRUG and H-Frame PartsTable C DC Link Fuse Upgrade Kit for G/M or H/N Size RGU // NRU (302104)Othe
DC Link Fuse Upgrade Kit for RGU in Parallel with NRU 3Safety PrecautionsThe following general precautions apply when servicing drives:Preliminary Ste
4 DC Link Fuse Upgrade Kit for RGU in Parallel with NRUMounting New RelayThe component designator for the new relay is CR5. The mounting locationvarie
DC Link Fuse Upgrade Kit for RGU in Parallel with NRU 5Figure 2 Mounting New Relay On E-Frame RGUG-Frame -Mount the new relay (CR5) in the control bay
6 DC Link Fuse Upgrade Kit for RGU in Parallel with NRUH-Frame -Mount the new relay (CR5) in the control bay - just to the left of CR4 andjust below T
DC Link Fuse Upgrade Kit for RGU in Parallel with NRU 71. Locate the fuses on the top of the power structure bay (the right-handbay). D-Frame and E-Fr
8 DC Link Fuse Upgrade Kit for RGU in Parallel with NRUWiring the New CircuitImportant:Use the enclosed stranded 14 gage wire (Belden 30614 orequivale
DC Link Fuse Upgrade Kit for RGU in Parallel with NRU 9Figure 9 Microswitch Circuit For RGU With Two FusesFigure 10 Microswitch Circuit For RGU With F